you are here:
coolex.pl
/
Products
/
compensation valve
COMPENSATION VALVE
The difference of pressure between a chamber and a surrounding are the result of atmospheric pressure changes, as well as the temperature changes inside of the chamber ( e.g. while cooling ). It may end with a complete devastation of its construction. Compensation valve (safety valve) is a device that prevents arising the difference between pressure in and outside the store. The valve construction assures keeping a chambers gas-tight. The device works reversible (sub pressure and overpressure). It must be filled with glycol (freezing temperature from -25C to -30C). Terminal’s diameter: 110mm. Max. size of a chamber 1000m3 You can use two or more valves at the same time in chambers bigger than 1000m3.
|